HVAC-How To Check The Windings Of a 3 Phase Compressor & Check For Any Grounds (A/C & Refrigeration)



How to troubleshoot a 3 phase compressor using a muli-meter
How to check a compressor for any grounds
How to check the windings of a 3 phase compressor
How to check resistance of a 3 phase compressor
How to ohm out a compressor

Camera Used: GoPro HERO8 Black

GoPro HERO8 Black (Camera Alone)
https://amzn.to/37Ngl3C

GoPro Hero8 Black Action Camera with Accessory Bundle
https://amzn.to/2Nub8EJ

This video shows you how to test a 3 phase compressor for any grounds as well as how to test the windings of a 3 phase compressor using a muti meter.

Checking for a grounded compressor:
From each 1 terminal to ground, you should read “O.L” indicating there is no ground if using resistance and there should be no audible sound if using continuity. If there was an audible sound indicating you have continuity or if you had a resistance reading then that would indicate you have a ground.

Checking the windings of a 3 phase compressor:
Between any 2 terminals in any combination, there should be a balanced reading meaning between any 2 terminals in any combination, you should have the same or very similar reading between the terminals when checking resistance indicating the windings are good. If you didn’t have a balanced reading between a set of 2 terminals, that would indicate the compressor has failed internally due to the windings.